Browse NSN 5925-00-153-7593 Listing of Circuit Breaker
It is our pleasure to inform you that part number TQB2130 listed under NSN 5925-00-153-7593 is now available and ready to ship from Fulfillment By ASAP. This part described as a Circuit Breaker manufactured by General Electric Co. If you’d like a quick quote for NSN 5925-00-153-7593, please fill out the form from below. Are you looking to have it delivered today or tomorrow? We can help! Simply complete the Request For Quote (RFQ) form given below to get started, and we will get back to you within 15 minutes!
Alternative NSN: 5925-00-153-7593 |
Item Name: Circuit Breaker |
Federal Supply Class (FSC): 5925 Circuit Breakers |
NIIN: 001537593 |
NCB Code: USA (00) |
Manufacturers: General Electric Co |
Part No | Manufacturer | Item Name | QTY | RFQ |
---|---|---|---|---|
TQB2130 | general electric co | circuit breaker | Avl | RFQ |
Characteristics Data of NSN 5925001537593
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 3.281 INCHES NOMINAL |
ADAT | BODY WIDTH | 2.000 INCHES MAXIMUM |
ADAU | BODY HEIGHT | 2.359 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.000 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.140 INCHES NOMINAL |
AKPX | POLE QUANTITY | 2 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 TERMINAL |
BBRG | III STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 18.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 125.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
PKWT | III UNPACKAGED UNIT WEIGHT | 8.000 OUNCES |
TTQY | TERMINAL TYPE AND QUANTITY | 4 COMPRESSION |